Terminal Block-to-Field (Signal) Wiring

106
ATTENTION: For CE conformity, the optional grounding bar
should be installed.
7. In each slot location not occupied by an I/O module, install a Filler
Block cover. (Part number 900TNF-0200).
CAUTION:
The Filler Block Cover looks much like an I/O Terminal
Block assembly, except that it does not include the wire
terminating block (screw terminals). The Filler Block Cover
mounts in the same manner as a Terminal Block (with
captured screws at top and bottom). Blank labels are
provided for mounting in the hinged door.
Terminal Block Wiring can be routed through the terminal block at
the top, at the bottom, or both. Wiring should be fixed in place using
wire ties at the slotted tabs that are molded in at top and bottom of
each terminal block. The terminal block is removable.
The optional Remote Termination Panel (RTP) provides an easy way to
connect the ControlEdge 900 Controller to the field wiring. The RTP
integrates some of the typical externally connected components,
reducing wiring and setup time. It also minimizes the need for
multiple wires under a single screw connection by expanding the
connectivity of the shared terminals of the I/O modules. See
"Installing RTP" on page 185 for more information.