Table 5-16: UIO for Analog Output Specification
Item
Field (loop) resistance
D-A conversion
Accuracy
116
side of the wire-pair.
Voltage input: This is because UIO supports only current
n
measurements.
Slide wire: This is because UIO supports only current
n
measurements.
Allowable field wiring resistance - UIO - Analog Input
channel
The maximum allowable field wiring resistance between the
transmitter and the connection terminal is dependent upon the
voltage requirement of the transmitter. The formula for calculating
the maximum wiring resistance for the UIO channel used as an
analog input is given by the following equation:
Rmax= [(19.0-Vtx) / (0.022)]
Where, Vtx=Voltage required at the transmitter terminal.

Field wiring for Analog Output

The UIO can drive 4-20mA. See the following list for AO specification:
No load restrictions: 6 channels with no other channels
n
configured.
With load restrictions:
n
channels into 250 ohm load with no other channels configured.
o
channels into 250 ohms remaining channels may be
o
configured for 1 DO and up to 10 digital inputs.
6 channels into 100 ohms with no other channels configured.
o
Description
Minimal 100 ohm
12 bit
< 0.5% of full scale including linearity
Figure 5-27: Field wiring for analog output