Component
Comments
Type
connects to UOC. All device IP addresses must be statically assigned.
For further information, see EtherNet IP User's Guide_EPDOC-X399-
en-510A.pdf.
Allen Bradley
The Rockwell Allen Bradley OPC Server from MatrikonOPC can be
OPC Server
installed on the Experion Server in systems which incorporate UOC.
from
The Matrikon OPC Server enables one of two methods whereby
MatrikonOPC
ControlLogix tag names can be used to make UDT references in a
UOC strategy. For further information, see EtherNet IP User's Guide_
EPDOC-X399-en-510A.pdf.
Studio 5000
Studio 5000 Logix Designer Software from Rockwell Allen Bradley is
Logix
used in conjunction with UOC configurations to configure IP
Designer
addresses of Rockwell Allen Bradley EtherNet/IP devices. It can also
Software
be used to export a file which defines ControlLogix tag names so that
they can be used in Control Builder to construct UDT data references
from UOC. For further information, see EtherNet IP User's Guide_
EPDOC-X399-en-510A.pdf.
While using DLR (Device Level Ring) on Stratix 5700 Switch, DO NOT
CONNECT a DLR network to a Non-DLR port on the Switch. DLR
should be connected only to the DLR ports on the switch. Doing this
will result in the entire down link network going down. The recovery is
to only remove the DLR connection from the switch.

Non-Redundant Star to 900 I/O and EIP Devices

In addition to the DLR ring topology, the UOC can also connect to a
non-redundant star EtherNet/IP network through its ETH3 downlink
port. This allows it to communicate simultaneously with ControlEdge
900 I/O as well as EtherNet/IP-capable I/O, devices and PLCs.
Installation and maintenance of a downlink EtherNet/IP network
must be done in accordance with the best practices of Ethernet
networking in general and EtherNet/IP in particular.
In this topology, CPMs connect through their ETH3 downlink port
with ETH4 port disconnected. EPMs connect through their ETH1 port
with ETH2 port disconnected. An example is shown in the diagram
below.