3.11.2

Error types

For information on the structure of the channel-related diagnostics, refer to the manual on
the interface module used in your ET 200S station.
1Count5V error types
The following table shows the error types on the 1Count5V.
Error class
1
00001: Short circuit
D
5
00101: Overtemperature
D
6
00110: Wire break
D
9
01001: Error
D
16
10000: Parameter assignment
D
error
26
11010: External error
D
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07
Meaning
Short circuit of the sensor supply or the
actuator.
The digital output is overloaded.
Line to the actuator is interrupted.
Internal module error occurred.
Parameters have not been assigned to
the module.
Wire break/short circuit of the 5 V
sensor signals:
A, /A, B, /B, N, /N,
3.11 Diagnostics
Remedy
Check the wiring to the sensor. Correct
the process wiring.
Correct the process wiring.
Correct the process wiring.
Replace the module.
Correct the parameter assignment.
Correct the parameter assignment.
1Count5V
225