2PULSE
5.4 Modes and Functions
Parameters of the "Pulse train" operating mode
Parameter
Operating mode
Time base
Function DI
On-delay
Pulse duration
1)
Time period
1)
Only if the short control interface is used
1)
If the long control interface is used, enter this value directly in the control interface.
292
Meaning
Set the "Pulse train" operating
mode.
Using the time base, select the
resolution and range of the
period duration, pulse duration,
and on-delay.
You can use the DI digital input
as an input or as a HW enable.
The time from the start of the
output sequence to the output
of the pulse train.
Pulse duration:
Enter the response time of the
actuator connected on your DO
digital output.
The period duration should
always be a multiple of the
response time of the actuator
connected to the DO digital
output.
Define the period duration
according to the required
repetition rate of the pulses.
You can change the time period
in your control program using
the "Time period factor".
Value range
Pulse output
Pulse width modulation
Pulse train
On/Off-delay
Frequency output
0.1 ms
1 ms
Input
HW enable
0 to 65535
With time base 0.1 ms:
2 to 65535
With time base 1 ms:
1 to 65535
If you violate the low limit of the
range, the 2PULSE sets the
pulse duration to 0.2 ms or 1
ms.
With time base 0.1 ms:
2 to 65535
With time base 1 ms:
1 to 65535
Operating Instructions, 06/2010, A5E00124867-07
Default
Pulse width
modulation
0.1 ms
Input
0
10000 → 1 s
20000 → 2 s
Technological Functions