3.7 Measurement Modes
3.7.11
Assignment of the Feedback and Control Interfaces for the Measurement
Modes
Note
For the 1Count5V, the following data of the control and feedback interface are consistent:
Bytes 0 to 3
Bytes 4 to 7
Bytes 8 to 11 (modified user data interface)
Use the access or addressing mode for data consistency over the entire control and
feedback interface on your master (only for configuration using the GSD file).
Assignment Tables
Table 3- 15
Feedback Interface (Inputs)
Address
Assignment
Bytes 0 to 3
Measured value
Byte 4
Bit 7: Short circuit of the encoder supply
Bit 6: Short circuit / wire break / overtemperature
Bit 5: Parameter assignment error
Bit 4: Short circuit / wire break / overtemperature
Bit 3: Short circuit / wire break / encoder signal
Bit 2: Resetting of status bits active
Bit 1: Load function error
Bit 0: Load function is running
Byte 5
Bit 7: Down direction status
Bit 6: Up direction status
Bit 5: Reserve = 0
Bit 4: DO2 status
Bit 3: DO1 status
Bit 2: Reserve = 0
Bit 1: DI status
Bit 0: Internal gate status
Byte 6
Bit 7: Reserve = 0
Bit 6: Low limit of measuring range
Bit 5: High limit of measuring range
Bit 4: Reserve = 0
Bit 3: Measurement completed
Bit 2: Reserve = 0
Bit 1: Reserve = 0
Bit 0: Reserve = 0
Byte 7
Reserve = 0
Bytes 8 to 11
Count value
Modified user data interface
1
188
1
Designation
ERR_24V
ERR_DO1
ERR_PARA
ERR_DO2
ERR_ENCODER
RES_STS_A
ERR_LOAD
STS_LOAD
STS_C_DN
STS_C_UP
STS_DO2
STS_DO1
STS_DI
STS_GATE
STS_UFLW
STS_OFLW
STS_CMP1
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07