5.7 Application Examples
First, you have to initialize the controller at a restart with the following STL program in
OB 100. Adapt the parameters of the FB 41 as required. The program furthermore sets the
factor for the time period to "10" (meaning that the active factor is 1.0) and sets the
SW_ENABLE bit to "1". This is used by the 2PULSE to start operation.
STL
CALL FB41,DB1
COM_RST
:=TRUE
MAN_ON
:=FALSE
PVPER_ON
:=TRUE
P_SEL
:=TRUE
I_SEL
:=TRUE
INT_HOLD
:=FALSE
I_ITL_ON
:=FALSE
D_SEL
:=FALSE
CYCLE
:=T#5MS
SP_INT
:=0.000000e+000
PV_IN
:=
PV_PER
:=
MAN
:=
GAIN
:=2.000000e+000
TI
:=T#10MS
TD
:=
TM_LAG
:=
DEADB_W
:=
LMN_HLM
:=1.000000e+002
LMN_LLM
:=0.000000e+000
PV_FAC
:=1.000000e+000
PV_OFF
:=0.000000e+000
LMN_FAC
:=1.000000e+000
LMN_OFF
:=0.000000e+000
I_ITLVAL
:=0.000000e+000
DISV
:=
LMN
:=
LMN_PER
:=
QLMN_HLM
:=
QLMN_LLM
:=
LMN_P
:=
LMN_I
:=
LMN_D
:=
PV
:=
ER
:=
L
10
T
PAB 259
L
1
T
PAB 258
344
Description
Reset controller block
Set the factor for the time period to 10
Set SW_ENABLE to 1
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07