Siemens SIMATIC ET 200S Operating Instructions Manual page 62

Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

1Count24V
2.7 Measurement Modes
Limit-Value Monitoring
The following value ranges are permitted for limit-value monitoring:
Encoder type
24-V encoders 0 to 99,999,999 × 10
Possible Measuring Ranges with Error Indication
Function of the Digital Input
For the "Function DI" parameter, select one of the following functions for the digital input:
● Input
● HW gate (see section "Gate Functions in Measurement Modes (Page 72)")
Function of the Digital Output DO1
For the "Function DO1" parameter, select one of the following functions for the DO1 digital
output:
● Output (no switching by the limit-value monitoring)
● Measured value outside the limits
● Measured value under the low limit
● Measured value over the high limit
(see section "Behavior of the Output in Measurement Modes (Page 73)")
Changing Values during Operation
The following values can be changed during operation:
● Low limit (LOAD_PREPARE)
● High limit (LOAD_VAL)
● Function of the Digital Output DO1 (C_DOPARAM)
● Integration time/update time (C_INTTIME)
(see section "Assignment of the Feedback and Control Interfaces for the Measurement
Modes (Page 75)")
62
Low limit f
u
Hz
-3
Frequency f
0.1 Hz
1 Hz
10 Hz
100 Hz
1 000 Hz
10 000 Hz
100 000 Hz
High limit f
o
f
+1 to 100,000,000 × 10
u
Absolute error
±0.001 Hz
±0.001 Hz
±0.003 Hz
±0.02 Hz
±0.18 Hz
±1.8 Hz
±18 Hz
Operating Instructions, 06/2010, A5E00124867-07
Hz
-3
Technological Functions