Siemens SIMATIC ET 200S Operating Instructions Manual page 124

Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

1Count5V
3.3 Brief instructions on commissioning the 1Count5V
Configuring with STEP 7 using HW Config
You must first adapt the hardware configuration of your existing ET 200S station.
1. Open the relevant project in SIMATIC Manager.
2. Open the HW Config configuration table in your project.
3. Select 1Count5V in the hardware catalog. The number 6ES7 138-4DE02-0AB0 C
4. Drag the entry to the slot at which you have mounted your 1Count5V.
5. Double-click this number to open the 1Count5V C (R-S Slot Number) tab.
6. Save and compile your configuration, and download the configuration in STOP mode of
Integration into the User Program (Not for Modified User Data Interface)
Create block FC 101 and integrate it in your control program (in OB 1, for example). This
block requires the DB1 data block with a length of 16 bytes. The start address of the module
in the following example is 256.
STL
Block: FC101
Network 1: Presettings
L
0
T
DB1.DBD0
T
DB1.DBD4
SET
S
DB1.DBX4.0
Network 2: Write to the control interface
L
DB1.DBD0
T
PAD 256
L
DB1.DBW4
T
PAW 260
124
appears in the infotext.
On the Addresses tab, you will find the addresses of the slot to which you have dragged
the 1Count5V. Make a note of these addresses for subsequent programming.
The Parameters tab contains the default settings for the 1Count5V. Leave the default
settings unchanged.
the CPU by choosing "PLC > Download to Module".
Description
//Delete control bits
//Open SW gate
//Write 6 bytes to the 1Count5V
//Configured start address of the outputs
Operating Instructions, 06/2010, A5E00124867-07