STL
Network 3: Read from the feedback interface
L
PED 256
T
DB1.DBD8
L
PED 260
T
DB1.DBD12
Testing
Use "Monitor/Modify Variables" to monitor the count value and the gate.
1. Select the "Block" folder in your project. Choose the "Insert > S7 Block > Variable Table"
2. Open the VAT 1 variable table, and enter the following variables in the "Address" column:
3. Choose "PLC > Connect To > Configured CPU" to switch to online.
4. Choose "Variable > Monitor" to switch to monitoring.
5. Switch the CPU to RUN mode.
6. Use your counting contact to generate pulses.
Result
You can now see that:
● The UP LED on the 1Count24V is on. The status of the UP LED changes with each new
● The count value in the block changes.
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07
menu command to insert the VAT 1 variable table, and then confirm with "OK".
DB1.DBD8 (current count value)
DB1.DBx13.0 (internal gate status)
The "internal gate status" bit must be set.
pulse.
2.3 Brief instructions on commissioning the 1Count24V
Description
//Read 8 bytes from the 1Count24V
//Configured start address of inputs
1Count24V
15