3.6.11

Parameter Assignment for the Count Modes

Introduction
You can use either of the following to assign parameters for the 1Count5V:
● STEP 7 V5.3 SP2 or later
● A GSD file (http://www.automation.siemens.com/csi/gsd)
Parameter List for Counting Modes
Table 3- 9
Parameter List for Counting Modes
Parameter
Enable
Group diagnostics
Response to failure of the higher-level controller
Response to CPU/master STOP
Encoder parameters
Signal evaluation A, B
Diagnostics A and B
Diagnostics N
Direction input B
Output parameters
Function DO1
Function DO2
Substitute value DO1
Substitute value DO2
Diagnostics DO1
1
Diagnostics DO2
1
Hysteresis DO1, DO2
Pulse duration [2 ms] DO1, DO2
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07
Value Range
Disable/enable
Turn off DO/
Continue working mode/
DO substitute a value/
DO keep last value
Rotary encoder single/double/quadruple
Off/on
Off/on
Normal/inverted
Output/
Switch on at counter status≥ comparison value/
Switch on at counter status≤ comparison value/
Pulse on reaching the comparison value/
Switch at comparison values
Output/
Switch on at counter status≥ comparison value/
Switch on at counter status≤ comparison value/
Pulse on reaching the comparison value
0/1
0/1
Off/on
Off/on
0...255
0...255
1Count5V
3.6 Count Modes
Default
Disable
Turn off DO
Rotary encoder single
Off
Off
normal
Output
Output
0
0
Off
Off
0
0
163