Periodic Counting - Siemens SIMATIC ET 200S Operating Instructions Manual

Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

1Count24V
2.6 Count Modes
2.6.4

Periodic Counting

Definition
In this mode, the 1Count24V counts periodically, depending on the assigned main count
direction ("Main count direction" parameter).
● When there is no main count direction:
● When the main count direction is up:
● When the count direction is down:
26
– Counts starting from the load value.
– Counts up or down.
– The count limits are fixed at the maximum count range.
– In the event of an overflow or underflow at the respective count limit, the 1Count24V
jumps to the load value and continues counting from there.
– Counts starting from the load value.
– Counts up or down.
– The upper limit can be assigned parameters, and the load value has a RESET status
of 0 and can be changed.
– When the high count limit is reached, the 1Count24V jumps to the load value and
continues counting from there.
– Counts starting from the load value.
– Counts up or down.
– When the low count limit is reached, the 1Count24V jumps to the load value and
continues counting from there.
– The low count limit is fixed at 0, and the load value can be assigned parameters
(parameter: high counting limit) and can be changed.
Figure 2-5
Periodic Counting without a Main Count Direction
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents