2PULSE
5.7 Application Examples
Parameters
The following parameters are required for channel 0 of the 2PULSE to pack piece goods in
pulse train mode.
Table 5- 3
Parameter List for the Packing of Piece Goods
Parameter
Group diagnostics
Diagnostics DO 0
Response to CPU/master STOP
Operating mode
Time base
Function DI 0
On-delay
Minimum pulse duration
Period
The parameters for Channel 1 are not relevant in this application example.
334
Set Value
Enable
On
Turn off DO 0
Pulse train
1 ms
HW enable
0
500
1000
Meaning
The following errors trigger a diagnostic
message:
Short circuit digital output
Short circuit of the encoder supply
The 2PULSE detects the short circuit error on
the digital output DO 0.
All the preset times are specified at a
resolution of 1 ms.
The pusher is controlled immediately with the
software enable.
This is 500 ms in the selected time base
This is 1 s in the selected time base. This
results in an interpulse period of 500 ms.