3.9 Position feedback
Table 3- 23
Control Interface (Outputs)
Address
Designation
Bytes 0 to 3
Byte 4
EXTF_ACK
RES_STS
CTRL_SYN
SW_GATE
Byte 5
LOAD_PREPARE
LOAD_VAL
Bytes 6 to 7
Not used for modified user interface
1
Notes on the Control Bits
Table 3- 24
Notes on the Control Bits
Control bits
Notes
CTRL_SYN
You use this bit to enable synchronization.
EXTF_ACK
Error acknowledgment
The error bits must be acknowledged with the EXTF_ACK control bit after the cause is removed.
LOAD_PREPARE
Load counter preparatory
The value from bytes 0 to 3 is applied as the load value.
LOAD_VAL
The value from bytes 0 to 3 is loaded directly as the new count value.
RES_STS
Start resetting of status bit
The status bits are reset by means of the acknowledgment process between the RES_STS bit and
the RES_STS_A bit.
SW_GATE
SW gate control bit
The SW gate is opened/closed by means of the control interface with the SW_GATE bit.
216
Assignment
Load value direct, preparatory, comparison value 1 or 2
Bit 7:
Error diagnostics acknowledgment
Bit 6:
Reserve = 0
Bit 5:
Reserve = 0
Bit 4:
Reserve = 0
Bit 3:
Reserve = 0
Bit 2:
Start resetting of status bit
Bit 1:
Enable synchronization
Bit 0:
SW gate control bit
Bit 7:
Reserve = 0
Bit 6:
Reserve = 0
Bit 5:
Reserve = 0
Bit 4:
Reserve = 0
Bit 3:
Reserve = 0
Bit 2:
Reserve = 0
Bit 1:
Load counter preparatory
Bit 0:
Load counter direct
Reserve = 0
1
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07