Siemens SIMATIC ET 200S Operating Instructions Manual page 355

Hide thumbs Also See for SIMATIC ET 200S:
Table of Contents

Advertisement

Assignment of the Feedback Interface
Address
Channel 0
Channel 1
Byte 0
Byte 4
Byte 1
Byte 5
Word 2
Word 6
Note
Depending on the interface module IM 151 and the configuration, the feedback value
(substitute value) supplied is 16#7FFF7FFF or 16#00000000.
Notes on the Control Signals
Control Signal
"Pulse output" operating mode:
Pulse duration
1) 2)
On-delay factor
1)
On-delay
2)
"Pulse width modulation" operating mode:
Output value
1) 2)
Time period factor
1)
Time period
2)
On-delay factor
2)
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07
5.9 Technical Specifications for Programming, Reference Lists
Assignment
Bit 7: ERR_24V
Bit 6: ERR_DO
Bit 5: ERR_PARA
Bit 4: ERR_PULS
Bit 3: ACK_SW_ENABLE
Bit 2: STS_DI
Bit 1: STS_DO
Bit 0: STS_ENABLE
Bit 0 to Bit 3: Sequence counter SEQ_CNT
Bit 4 to Bit 7: Reserve = 0
Measured value of the current
Notes
The time that is set for the DO digital output on expiration of the on-
delay.
You can change the configured on-delay before the start of the output
sequence:
On-delay = Factor × 0.1 × configured on-delay
The time from the start of the output sequence to the output of the pulse
train.
Value that is output with pulse-width modulation at the DO digital output
on expiration of the on-delay.
You can change the configured period duration:
Period duration = Factor × 0.1 × configured period duration
When specifying the time period take into account the set minimum
pulse duration and the response time of your final controlling element
that is connected to the digital output DO.
You can change the configured on-delay before the start of the output
sequence:
On-delay = Factor × 0.1 × configured on-delay
2PULSE
355