Control and feedback signals of the "Frequency output" operating mode
Control and feedback
signals
Control signals when the short control interface is used (8 bytes)
Software enable
(SW_ENABLE)
Output value
On-delay factor
Control signals when the long control interface is used (12 bytes)
Software enable
(SW_ENABLE)
Output value
On-delay
Technological Functions
Operating Instructions, 06/2010, A5E00124867-07
Meaning
Starting and canceling of the
output sequence.
The value that is output in
frequency format on the digital
output DO.
The on-delay that has been
assigned parameters can be
changed before the start of the
output sequence:
On-delay = Factor x 0.1 x
configured on-delay
Starting and canceling of the
output sequence.
The value that is output in
frequency format on the digital
output DO.
The on-delay can be changed
before the start of the output
sequence.
Value range
0 = SW_ENABLE canceled
1 = SW_ENABLE set 0→1 = start
of output sequence; may be
dependent on the hardware
enable
Depending on the output format:
1 Hz: 0 ... 5000
S7 analog output:
0 to 27648
If you enter an output value >
5000 or 27648, the 2PULSE limits
this to 5000 or 27648.
0 to 255
If the on-delay <0.2 ms or if factor
= 0, the effective on-delay is = 0.
If there is an on-delay > 65.535 s,
the on-delay is limited to 65.535 s.
0 = SW_ENABLE canceled
1 = SW_ENABLE set 0→1 = start
of output sequence; may be
dependent on the hardware
enable
Depending on the output format:
1 Hz: 0 ... 5000
S7 analog output:
0 to 27648
If you enter an output value >
5000 or 27648, the 2PULSE limits
this to 5000 or 27648.
0 to 65535
On-delay = Time basis x Specified
numerical value
2PULSE
5.4 Modes and Functions
Channel 0
Channel 1
address
address
Byte 2:
Byte 6:
Bit 0
Bit 0
Word 0
Word 4
Byte 3
Byte 7
Byte 4:
Byte 10:
Bit 0
Bit 0
Word 0
Word 6
Word 2
Word 8
307