Defrost Operation; Drain Pan Heater (Option) - Daikin RXYQ-TA Series Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
7.4

Defrost Operation

To defrost the outdoor heat exchanger while in evaporator, the defrost operation is conducted to recover the
heating capacity.
Tc : High pressure equivalent saturation temperature
Te : Low pressure equivalent saturation temperature
Starting conditions
Referring to the set conditions for the following items, start the defrost operation.
• Heat transfer coefficient of the outdoor heat exchanger
• Heat exchanger deicer temperature (Tb)
• Timer (Set to 2 hours at minimum.)
Furthermore, the heat transfer coefficient of the outdoor unit Evaporator is computed from Tc, Te, and
compressor loads.
Part Name
Inverter compressor 1
Inverter compressor 2
Inverter fan 1
Inverter fan 2
Electronic expansion
valve (Main)
Electronic expansion
valve (Injection)
Four way valve
Solenoid valve
(Accumulator oil return)
Solenoid valve
(Oil return 1)
Solenoid valve
(Oil return 2)
Ending conditions
: equipped
–: not equipped
∗1: RXYQ96/120TA only
Electronic expansion valve
7.5

Drain Pan Heater (Option)

When the drain pan heater is connected, it operates below.
Operating conditions
Outdoor air temperature < 3°C (37.4 °F)
&
During defrost operation
Functions and Control
Electric
Symbol RXYQ72-120TA RXYQ144/168TA
M1C
M2C
M1F
∗1
M2F
( )
Y1E
Y2E
Y1S
Y2S
Y3S
Y4S
Indoor unit actuator
Thermostat ON unit
Fan
Stopping unit
Thermostat OFF unit
Thermostat ON unit
Stopping unit
Thermostat OFF unit
Operation
RXYQ72TA: 266 Hz
RXYQ96/120TA: 188 Hz
RXYQ144/168TA: 252 Hz + 252 Hz
With high pressure
OFF ←→ Step 4 ←→ Step 6
RXYQ72TA: 480 pulses
RXYQ96-168TA: 3,000 pulses
0 pulse
OFF
ON
ON
• A lapse of 15 min.
OR
• Tb > 11°C (51.8°F) continues for 30 sec. or more
During defrost
OFF
OFF
OFF
Defrost EV opening degree
Defrost EV opening degree
Defrost EV opening degree
Special Control
70