Error Codes And Descriptions - Daikin RXYQ-TA Series Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

Service Check Function
2.3

Error Codes and Descriptions

Error code
A0
Indoor Unit
A1
A3
A6
A7 (∗1)
A8
A9
AF (∗1)
AJ
C1
C4
C5
C6
C9 (∗2)
CA
CC
CE (∗1)
CJ (∗2)
Outdoor Unit
E1
E2
E3
E4
E5
E6
E7
E9
F3
F4
F6
H3
H7
H9
J3
J5
J6
J7
J8
J9
171
Operation
lamp
l
External protection device abnormality
l
Indoor unit PCB abnormality
l
Drain level control system abnormality
l
Fan motor lock, overload
Indoor fan motor abnormality
Overload/overcurrent/lock of indoor fan motor
Blower motor not running
Indoor fan motor status abnormality
Low indoor airflow
k
Swing flap motor abnormality
l
Power supply voltage abnormality
Blower motor stops for over/under voltage
l
Electronic expansion valve coil abnormality, dust clogging
k
Drain level above limit
l
Capacity determination device abnormality
l
Transmission abnormality between indoor unit PCB and fan PCB
Blower motor communication error
l
Heat exchanger liquid pipe thermistor abnormality
l
Heat exchanger gas pipe thermistor abnormality
l
Combination error between indoor unit PCB and fan PCB
Blower motor HP mismatch
Indoor blower does not have required parameters to function
l
Suction air thermistor abnormality
Remote sensor abnormality
l
Discharge air thermistor abnormality
k
Humidity sensor system abnormality
k
Infrared presence/floor sensor error
k
Remote controller thermistor abnormality
l
Outdoor unit main PCB abnormality
l
Current leakage detection
Missing of leakage detection core
l
Actuation of high pressure switch
l
Actuation of low pressure sensor
l
Inverter compressor motor lock
l
Compressor damage alarm
l
Outdoor fan motor abnormality
l
Electronic expansion valve coil abnormality
l
Discharge pipe temperature abnormality
l
Wet alarm
l
Refrigerant overcharged
l
Harness abnormality (between outdoor unit main PCB and inverter PCB)
l
Outdoor fan motor signal abnormality
l
Outdoor air thermistor (R1T) abnormality
l
Discharge pipe thermistor (R21T, R22T) abnormality
Compressor body thermistor (R8T) abnormality
l
Accumulator inlet thermistor (R3T) abnormality
l
Heat exchanger deicer thermistor (R7T) abnormality
l
Subcooling heat exchanger liquid pipe thermistor (R5T) abnormality
l
Heat exchanger liquid pipe thermistor (R4T) abnormality
l
Heat exchanger gas pipe thermistor (R6T) abnormality
Error contents
SiUS341615E
k: ON
h: OFF
l: Blink
Reference
page
174
176
177
179
182
186
187
188
189
190
192
193
194
195
196
197
199
200
200
201
202
203
200
204
200
205
206
211
212
213
214
215
217
219
221
223
226
228
230
232
233
234
235
235
235
235
235
235
235
Service Diagnosis