3.2

Indoor Unit PCB Abnormality

A1
Error Code
Applicable
All indoor unit models
Models
Method of Error
Check data from EEPROM.
Detection
Error Decision
When data could not be correctly received from the EEPROM
Conditions
EEPROM : Type of nonvolatile memory. Maintains memory contents even when the power supply
Supposed
Causes
Troubleshooting
Service Diagnosis
is turned OFF.
Defective indoor unit PCB
External factor (Noise etc.)
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn the power supply OFF,
then the power ON again.
Does the
system return to
normal?
NO
YES
Troubleshooting by Error Code
The indoor unit main PCB
(A1P) is normal.
External factor other than
error (for example, noise
etc.).
Replace the indoor unit main
PCB (A1P).