Daikin RXYQ-TA Series Service Manual page 61

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
Maintenance Menu
Indoor Unit Status
Outdoor Unit Status
Forced Defrost
Error Display
Swap Unit No.
Addressed Sensor
Value
∗1. (For FXTQ-TA models)
The actual fan speed is converted into the fan tap to be displayed. Therefore, if the fan speed is changed by
controls or external factors, the airflow rate set with the remote controller may differ from the fan tap display.
∗2. (For FXTQ-TA models)
0 rpm is displayed even if the fan is rotating.
∗3. (For FXTQ-TA models)
The ON/OFF status of the humidifier connected to HUMIDIFIER on the X1M terminal of the indoor unit PCB is
not displayed. The ON/OFF status of the humidifier connected to the wiring adaptor is displayed.
Remote Controller
Item 2
10.FLOAT
11.T1/T2
12.Th1
13.Th2
14.Th3
15.Th4
16.Th5
17.Th6
1. Unit No.
2. FAN step
3. COMP
4. EV1
5. SV1
6. Th1
7. Th2
8. Th3
9. Th4
10.Th5
11.Th6
1. Forced defrost ON
2. Forced defrost OFF
1. Display Error ON
2. Display Error OFF
3. Display Warning ON
4. Display Warning OFF
1. Current Unit No.
2. Transfer Unit No.
Unit No.: 0 - 15
Code
00:
01:
02:
03:
04:
05:
06:
07:
08:
09:
Data
FLOAT SWITCH ON/OFF
T1/T2 input from outside ON/OFF
Suction air thermistor
Heat exchanger liquid pipe thermistor
Heat exchanger gas pipe thermistor
Discharge air thermistor
Select the Unit No. you want to check.
Fan tap
Compressor power supply frequency (Hz)
Degree that electronic expansion valve is open (pulse)
Solenoid valve ON/OFF
Enables the forced defrost operation.
Disables the forced defrost operation.
Displays the error on the screen.
Displays neither errors nor warnings.
Displays a warning on the screen if an error occurs.
No warning is displayed.
A unit No. can be transferred to another.
Select the Unit No. you want to check.
Remote controller thermistor (°C)
Suction air thermistor (°C)
Heat exchanger liquid pipe thermistor (°C)
Heat exchanger gas pipe thermistor (°C)
Indoor unit address No.
Outdoor unit address No.
Branch selector unit address No.
Zone control address No.
Cooling/Heating batch address No.
Demand/low-noise address No.
The corresponding data will be displayed, based on the Unit No.
and Code selected.
Service Mode
Remarks
48