Daikin RXYQ-TA Series Service Manual page 231

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
∗1. Make a comparison between voltage measured by the pressure sensor and that read by the
Note:
CHECK 2
CHECK 12
Service Diagnosis
pressure gauge.
(The pressure sensor makes measurement of voltage at its connector block to convert it to
pressure.
CHECK 12
)
Refer to page 292.
Refer to page 302.
Troubleshooting by Error Code
218

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents