Wireless Remote Controller - Daikin RXYQ-TA Series Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
1.2

Wireless Remote Controller

To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
Step
Action
1
Press the INSPECTION/TEST button for 4 seconds during normal mode to enter
the field setting mode.
2
Press the MODE button to select the desired mode No.
3
Press the UP button to select the first code No.
4
Press the DOWN button to select the second code No.
5
Press the RESERVE button to confirm the setting.
6
Press the INSPECTION/TEST button to return to the normal mode.
Field Settings
Mode No.
Field setting mode
RESERVE button
First code No.
Second code No.
Field Setting from Remote Controller
UP button
DOWN button
MODE button
INSPECTION/TEST button