Daikin RXYQ-TA Series Service Manual page 127

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
Interlocked Operation between Humidifier and Drain Pump
This is used to interlock the humidifier with the drain pump. When water is drained out of the unit, this setting is
unnecessary.
Mode No.
15 (25)
Individual Setting of Ventilation
This is set to perform individual operation of Energy recovery ventilator using the remote controller/central unit
when Energy recovery ventilator is built in.
(Switch only when Energy recovery ventilator is built in.)
Mode No.
15 (25)
Display of Contact Center (For BRC1E73 only)
You can turn OFF the display of "DAIKIN Contact Center" as "Contact for Service Display."
Mode No.
1b (2b)
Display of Error Codes on the Remote Controller (For BRC1E73 only)
Error code (four digits) is displayed for limited products.
Select two-digit display if four-digit display is not preferred.
Mode No.
1b (2b)
Key-lock Pattern Settings (For BRC1E73 only)
Setting of key-lock pattern for the remote controller
Mode No.
1b (2b)
∗ When the Second code No. is set to 04, no menu operation is allowed without key-lock by pressing and holding
the menu button. Set the Second code No
Field Settings
First Code No.
Second Code No.
3
First Code No.
Second Code No.
5
First Code No.
Second Code No.
3
First Code No.
Second Code No.
4
First Code No.
Second Code No.
12
.
01
Interlocked operation between humidifier and drain
02
01
02
01
02
01
02
03
04
01
02
(Cancel procedure is not displayed.)
03
04
No menu operation is allowed any time.
to other than 04 to cancel it.
Field Setting from Remote Controller
Contents
Individual operation of humidifier
pump
Contents
Not equipped
Individual operation of ventilation
Contents
Displayed
Not displayed
Contents
Two-digit display
Four-digit display
Contents
No operation allowed
(Cancel procedure is displayed.)
No operation allowed
No menu operation is allowed.
114