Daikin RXYQ-TA Series Service Manual page 116

Heat pump 60 hz
Table of Contents

Advertisement

Field Setting from Remote Controller
1.4.2 Detailed Explanation of Setting Modes
Filter Sign Setting
If switching the filter sign ON time, set as given in the table below.
Mode No.
10 (20)
Ultra Long Life Filter Sign Setting
When a Ultra long life filter is installed, the filter sign timer setting must be changed.
Mode No.
10 (20)
Filter Cleaning Sign Time
The filter cleaning sign display time can be changed.
FXTQ-TA
Mode No.
10 (20)
Selection of Thermistor
Select a thermistor to control room temperature.
When the unit is not equipped with an infrared floor sensor:
Mode No.
10 (20)
The factory setting for the Second Code No. is 01 and room temperature is controlled by the suction air
thermistor and remote controller thermistor.
When the Second Code No. is set to 02, room temperature is controlled by the suction air thermistor.
When the Second Code No. is set to 03, room temperature is controlled by the remote controller thermistor.
FXTQ-TA
Mode No.
10 (20)
When the Second Code No. is set to 02, room temperature is controlled by the remote sensor thermistor.
When the Second Code No. is set to 03, room temperature is controlled by the remote controller thermistor.
103
First Code
Second
No.
Code No.
01
0
02
First Code No.
Second Code No.
1
First Code No.
Second Code No.
1
First Code No.
Second Code No.
2
First Code No.
Second Code No.
2
Standard
Long Life
Filter
Filter
200 hrs.
2,500 hrs.
100 hrs.
1,250 hrs.
01
02
01
02
Remote controller thermistor and suction air
01
thermistor for indoor unit
02
Suction air thermistor for indoor unit
03
Remote controller thermistor
01
02
Remote sensor thermistor
03
Remote controller thermistor
Ultra Long Life
Contents
Filter
10,000 hrs.
Contamination Light
5,000 hrs.
Contamination Heavy
Contents
Long Life Filter
Ultra Long Life Filter
Contents (Light/Heavy)
2,500/1,250 hours
10,000/5,000 hours
Contents
Contents
SiUS341615E
Field Settings

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents