Daikin RXYQ-TA Series Service Manual page 157

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
No.
Item
∗1
96 Auxiliary heater
maximum
allowable
temperature
97 Auxiliary heater
maximum
allowable
temperature
release
differential
∗1: Numbers in the "No." column represent the number of times to press the BS button.
∗ : Setting does not return to factory setting when exit mode 2. To cancel the function, change setting manually
to factory setting.
∗ : Once function is activated t01 appears. To stop current function, press once BS3 "Return" button.
For detailed description about each setting, refer to "Description Field Settings (mode 2: m2) on Outdoor Unit
Main PCB" on page 145.
Indication
bold
Field Settings
Description
Auxiliary heater is allowed to energize
when the ambient temperature is smaller
than the auxiliary heater maximum
allowable temperature.
Auxiliary heater is not allowed to energize
when the outdoor ambient temperature is
recovered by differential above the
auxiliary heater maximum allowable
temperature.
means factory setting.
Field Settings for Outdoor Unit
7 segment
display
Description
SEG
SEG
SEG
1
2
3
–17.7°C (0°F)
–15°C (5°F)
–12.2°C (10°F)
–9.4°C (15°F)
–6.6°C (20°F)
–3.8°C (25°F)
–1.1°C (30°F)
1.6°C (35°F)
2.
9
6
4.4°C (40°F)
7.2°C (45°F)
10°C (50°F)
12.7°C (55°F)
15.5°C (60°F)
18.3°C (65°F)
Auxiliary heater always not allowed
Auxiliary heater always allowed
2.8°C (5°F)
2.
9
7
5.6°C (10°F)
8.3°C (15°F)
7 segment
display
Range
SEG
SEG
SEG
1
2
3
0
1
2
3
4
5
6
7
8
9
1
0
1
1
1
2
1
3
1
4
1
5
0
1
2
144