Reheat

This mode will prevent the domestic hot water from cooling down
lower than a certain temperature. When enabled the indoor unit will
deliver hot water to the domestic hot water tank when the reheat
minimum value is reached. The domestic water heating will continue
until the reheat maximum temperature is reached.
Selecting reheat operation for domestic water heating
1
Use the
button to enable reheat operation.
The
icon will display.
INFORMATION
Remark that the
as the reheat function is enabled. It is not possible to
see when the indoor unit is reheating the domestic hot
water tank.
2
Press the
button again to disable reheat operation.
The
icon disappears.
The reheat minimum and reheat maximum temperature set points
are field settings. Refer to
"5.12. Field settings" on page 18
detailed description how to set one or more field settings.
I
[b-00] Set point: reheat minimum temperature (see figure
"Domestic water heating modes" on page
I
[b-01] Set point: reheat maximum temperature (see figure
"Domestic water heating modes" on page
INFORMATION
Remark that pushing the
the domestic water heating. Domestic water heating is only
switched on or off by means of the
disabling the storage schedule timer.

Disinfection operation

This mode will disinfect the domestic hot water tank by periodically
heating the domestic water to a specific temperature. During the
operation of this mode the
second intervals.
INFORMATION
Remark that the
effective operation.
During the operation it is always possible to cancel the
disinfection function by pushing the
Be aware that after pushing the
that the permanently lit
the reheat function is enabled.
NOTICE
If a domestic hot water tank is installed, the disinfection
function is enabled by default.
The disinfection temperature set point is a field setting as are the
retention time, day and hour. Refer to
for a detailed description how to set one or more field settings.
I
[4-00] Status: defines whether the disinfection function is turned
ON (1) or OFF (0).
I
[4-01] Operation interval: day of the week at which the domestic
water should be heated.
I
[4-02] Start time: time at which the disinfection operation is
started.
I
[5-00] Set point: Disinfection water temperature to be reached
(see figure
"Domestic water heating modes" on page
I
[5-01] Duration: time period defining how long the disinfection
set point temperature should be maintained.
Even if all schedule timers are de-activated and there is no reheat
function active, the disinfection function will operate if a domestic hot
water tank is installed and field setting [4-00] is set to ON.
HXHD125A8V1B
VRV IV system indoor unit
4P404572-1 – 2015.04
icon will be continuously lit as long
8).
8).
button has no influence on
button and/or
icon will be blinking rapidly with 0.5
icon will only be blinking during
button once.
button, it is possible
icon still displays, meaning that
"5.12. Field settings" on page 18
8).

5.5. Other operation modes

Start up operation (
During start up, the
pump is starting up and is not working in a steady state condition.
Defrost operation (
In space heating operation or domestic water heating operation,
freezing of the outdoor heat exchanger may occur due to low outdoor
temperature. If this risk occurs, the system goes into defrost
operation. During defrost operation, space heating or domestic hot
water operation is not possible.
Quiet mode operation (
Quiet mode operation means that the indoor unit works at reduced
compressor speed so that the noise produced by the indoor unit
drops. This implies that it will take longer till the required temperature
set point is reached. Beware of this when a certain level of heating is
required indoors.
for a
Selecting quiet mode operation
1
Use the
button to activate quiet mode operation.
The
icon displays.
If the controller is set to permission level 2 or 3 (refer to "Field
settings" in the installation manual), the
operable.
2
Press the
The
icon disappears.
There are 3 different levels of quiet mode operation. The desired
quiet mode is set through a field setting. Refer to
settings" on page 18
field settings.
I
[8-03] Status: defines the level of low noise operation (quiet
mode).
)
icon displays, indicating that the heat
)
)
button again to deactivate quiet mode operation.
for a detailed description how to set one or more
button is not
"5.12. Field
Operation manual
10