Capacity Range; Combination Ratio; Outdoor Unit Combinations - Daikin RXYQ-TA Series Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

Capacity Range

4. Capacity Range
4.1

Combination Ratio

Combination ratio =
Type
Single outdoor units
Double outdoor units
Triple outdoor units
Notes: ∗1. If the operational capacity of indoor units is more than 130%, low airflow operation is enforced in all the
indoor units. Refer to the table below.
∗2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total
connection capacity of the outdoor-air processing units (FXMQ-MF) must not exceed 30% of the capacity
index of the outdoor units. And the connection ratio must not exceed 100%.
Indoor unit fan tap setting
Indoor units fan speed limitation related to connection capacity and outdoor air temperature for energy saving.
Default value = 0
Value [2-34]
Fan speed is limited to L tap when indoor units capacity ≥ 130%.
0
In heating mode, fan speed is limited to L tap when indoor units capacity ≥ 130%.
1
2
Fan speed follows a setting of the remote controller (not limited by indoor units connection capacity).
Fan speed is limited to L tap when outdoor air temperature goes down to below 29.5°C (85.1°F). It returns to remote
3
controller setting when outdoor air temperature goes up to over 32.5°C (90.5 °F).
Fan speed is limited to L tap when outdoor air temperature goes down to below 23.5°C (74.3°F). It returns to remote
4
controller setting when outdoor air temperature goes up to over 26.5°C (79.7°F).
Fan speed is limited to L tap when outdoor air temperature goes down to below 19.3°C (66.7°F). It returns to remote
5
controller setting when outdoor air temperature goes up to over 22.3°C (72.1°F).
4.2

Outdoor Unit Combinations

Capacity Range
RXYQ
Max. Number of
Connectable Indoor Units
Total Capacity Index of
Indoor Units to be
Connected ∗1
Capacity Range
RXYQ
Max. Number of
Connectable Indoor Units
Total Capacity Index of
Indoor Units to be
Connected ∗1
Note: ∗1. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single
outdoor units, 160% for double outdoor units, and 130% for triple outdoor units.
7
Total capacity index of the indoor units
Capacity index of the outdoor units
Types of connected indoor units
Min.
combination
When using
ratio
only FXDQ,
FXMQ-PB,
FXAQ
200% ∗1
50%
6 ton
8 ton
10 ton
72TAYDU
96TAYDU
120TAYDU
72TATJU
96TATJU
120TATJU
12
16
36~93
48~124
60~156
(144)
(192)
(240)
24 ton
26 ton
28 ton
288TAYDU
312TAYDU
336TAYDU
288TATJU
312TATJU
336TATJU
49
54
144~374
156~405
168~436
(461)
(499)
(538)
Max. combination ratio
When using
only FXTQ,
Other indoor
or at least one
unit models
FXFQ07 or
FXFQ09
200% ∗1
160% ∗1
130%
130%
Indoor unit fan tap setting
12 ton
14 ton
144TAYDU
168TAYDU
144TATJU
168TATJU
20
25
29
72~187
84~218
(288)
(336)
30 ton
32 ton
360TAYDU
384TAYDU
360TATJU
384TATJU
58
62
64
180~468
192~499
(468)
(499)
Type of connected air treatment equipments
FXMQ-MF
When FXMQ-MF and
When FXMQ-MF is only
connected
100%
16 ton
18 ton
192TAYDU
216TAYDU
240TAYDU
192TATJU
216TATJU
240TATJU
33
37
96~249
108~280
120~312
(307)
(346)
34 ton
36 ton
408TAYDU
432TAYDU
456TAYDU
408TATJU
432TATJU
456TATJU
64
64
204~530
216~561
228~592
(530)
(561)
SiUS341615E
indoor units are
connected
100% ∗2
20 ton
22 ton
264TAYDU
264TATJU
41
45
132~343
(384)
(422)
38 ton
64
(592)
General Information