SiUS341615E
8.2.2 With Optional Infrared Floor Sensor
The relationship between remote controller set temperature and control target temperature is
described below.
Examples are given to illustrate a control target temperature that satisfies the remote controller set
temperature.
Regarding control target temperature
When using the infrared floor sensor, the temperature around people will be treated as the control
target temperature for operation.
What is the temperature around people?
The temperature around people refers to the temperature of the living space, obtained from the
temperature around the ceiling and the temperature underfoot. The temperature is calculated using
the detected values of the suction air thermistor and the infrared floor sensor.
It is difficult to use only suction air temperature control for underfoot air conditioning.
Functions and Control
The temperature difference for cooling ⇔ heating mode switching is 5°C (9°F).
When using the floor temperature as the control target, the remote controller set temperature is
equal to the actual control target temperature in heating operation.
The above also applies to automatic operation.
When setting the suction air thermistor (Default setting)
Temperature
Remote controller set temperature
Cooling
Control target temperature
Remote controller set temperature
Heating
Control target temperature
When using the remote controller thermistor (Field setting is required)
Temperature
Remote controller set temperature
Cooling
Control target temperature
Remote controller set temperature
Heating
Control target temperature
Outline of Control (Indoor Unit)
˚C
˚F
˚C
˚F
74