Swing Flap Motor Abnormality - Daikin RXYQ-TA Series Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E

3.10 Swing Flap Motor Abnormality

A7
Error Code
Applicable
FXFQ, FXZQ, FXUQ, FXEQ, FXHQ, FXAQ
Models
Method of Error
Utilizes ON/OFF of the limit switch when the motor turns.
Detection
Error Decision
When ON/OFF of the micro-switch for positioning cannot be reversed even though the swing flap
Conditions
motor is energized for a specified amount of time (about 30 seconds).
∗ Error code is displayed but the system operates continuously.
Supposed
Causes
Troubleshooting
Service Diagnosis
Defective swing motor
Defective connection cable (power supply and limit switch)
Defective airflow direction adjusting flap-cam
Defective indoor unit main PCB
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is power supply 208-
230 V provided?
YES
Indoor unit is
a model equipped with a
swing flap function
YES
The swing
motor works when
the power supply is turned OFF
and then restart.
NO
After
turning
the swing-flap
ON and then
stopping with the
remote controller, the
voltage of the connector
(∗1) is 208-230 VAC
when turned ON
again (within 30
seconds of
turning ON
again).
YES
A
NO
NO
The
YES
connector is
connected to the indoor
unit PCB. (∗1)
YES
The limit switch
functions normally.
YES
The relay
cable is short circuited
or disconnected.
NO
NO
Troubleshooting by Error Code
Provide 208-230 V power
supply.
Replace the indoor unit main
PCB (A1P).
NO
Connect the connector (∗1)
and turn the power supply on
again.
NO
Replace the defective
swing motor. (∗2)
YES
Replace the limit switch
relay cable.
Replace the indoor unit main
PCB (A1P).
190

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents