Daikin RXYQ-TA Series Service Manual page 129

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
1.4.3 Outdoor-Air Processing Unit - Field Setting (Remote Controller)
First
Mode
Setting Contents
Code
No.
No.
Filter
0
contamination
10
Display time to
(20)
3
clean air filter
calculation
External ON/OFF
1
input
12
(22)
Power failure
5
automatic reset
Discharge
pipe
3
temperature
(cooling)
14
(24)
Discharge
pipe
4
temperature
(heating)
1.4.4 Setting of Operation Control Mode from Remote Controller
(Field Setting)
The operation control mode is compatible with a variety of controls and operations by limiting the functions of the
operation remote controller. Furthermore, operations such as remote controller ON/OFF can be limited in
accordance with the combination conditions. (Refer to information in the next page.)
Central remote controller is normally available for operations. (Except when centralized monitor is connected)
1.4.5 Contents of Control Modes
20 modes consisting of combinations of the following 5 operation modes with temperature and operation mode
setting by remote controller can be set and displayed by operation modes 0 through 19.
ON/OFF control impossible by remote controller
Used when you want to turn ON/OFF by central remote controller only.
(Cannot be turned ON/OFF by remote controller.)
OFF control only possible by remote controller
Used when you want to turn ON by central remote controller only, and OFF by remote controller only.
Centralized
Used when you want to turn ON by central remote controller only, and turn ON/OFF freely by remote
controller during set time.
Individual
Used when you want to turn ON/OFF by both central remote controller and remote controller.
Timer operation possible by remote controller
Used when you want to turn ON/OFF by remote controller during set time and you do not want to start
operation by central remote controller when time of system start is programmed.
Field Settings
01
02
2500hr
1250hr
No
Display
display
Forced
ON/OFF
OFF
control
Not
equipped Equipped
°C
13
14
°F
55.4
57.2
°C
18
19
°F
64.4
66.2
Second Code No.
03
04
05
06
07
15
16
17
18
19
59
60.8 62.6 64.4 66.2
20
21
22
23
24
68 69.8 71.6 73.4 75.2 77 78.8 80.6 82.4 84.2
Field Setting from Remote Controller
: Factory setting
08
09
10
11
12
20
21
22
23
24
68
69.8 71.6 73.4 75.2
25
26
27
28
29
13
14
15
25
25
25
77
77
77
30
30
30
86
86
86
116