Daikin RXYQ-TA Series Service Manual page 154

Heat pump 60 hz
Table of Contents

Advertisement

Field Settings for Outdoor Unit
2.6.1 List of Setting Mode (Mode 2)
This overview shows the available settings by using the press buttons on the outdoor unit PCB.
No.
Item
Description
∗1
0
COOL/HEAT
Several systems as 1 zone change over
selection
COOL/HEAT:
1
COOL/HEAT
Used to make address setting for unified
unified address
cooling/heating operation.
2
Low noise/
Used to make address setting for low noise/
demand address
demand operation.
5
Indoor fan forced
Used to force the fan of indoor unit to H tap.
H
6
Forced
Used to force all indoor units to operate
thermostat
forced thermostat ON.
8
Te setting
Used to make setting of targeted
evaporating temperature for cooling
operation.
9
Tc setting
Used to make setting of targeted
condensing temperature for heating
operation.
12 External low
Used to receive external low noise or
noise setting/
demand signal.
demand setting
13 AIRNET address Used to set address of AIRNET
16 Heat pump
Used for heat pump lockout
lockout 1
18 High ESP setting
Fan high static pressure setting
FAN
20 Additional
Used to perform additional refrigerant
refrigerant
charging operation (compressor operation).
charge
21 Refrigerant
Used to set the system to refrigerant
recovery and
recovery mode (without compressor run).
vacuuming
22 Automatic night-
Automatic night-time low noise operation.
time low noise
Time for the operation is subject to the start
operation
and end time settings.
25 External low
Low noise level when the external low noise
noise level
signal is input at option DTA104A61.
141
INDIVIDUAL: VRV indoor unit or A-B-C
input set mode.
MASTER: System is the COOL/HEAT
master unit.
SLAVE: System is not a COOL/HEAT
master.
7 segment
display
Description
SEG
SEG
SEG
1
2
3
Individual
2.
0
0
Unified master
Unified slave
2.
0
1
Address
2.
0
2
Address
Normal operation
2.
0
5
Indoor fan H
Normal operation
2.
0
6
Forced thermostat ON
Auto (6-11°C) (42.8-51.8°F)
Standard: 6°C (42.8°F)
High sensible: 7°C (44.6°F)
2.
0
8
High sensible: 8°C (46.4°F)
High sensible: 9°C (48.2°F)
High sensible: 10°C (50.0°F)
High sensible: 11°C (51.8°F)
Auto (38-46°C) (100.4-114.8°F)
Low: 41°C (105.8°F)
2.
0
9
Normal: 43°C (109.4°F)
High: 46°C (114.8°F)
Input LNO/DE
2.
1
2
2.
1
3
Address
OFF
2.
1
6
ON
OFF
2.
1
8
ON
Refrigerant charging
2.
2
0
OFF
ON
Refrigerant recovery
2.
2
1
OFF
ON
OFF
Level 1
2.
2
2
Level 2
Level 3
Level 1
2.
2
5
Level 2
Level 3
SiUS341615E
7 segment
display
Range
SEG
SEG
SEG
1
2
3
0
1
2
0
0
3
1
31
0
0
3
1
31
0
1
0
1
0
2
3
4
5
6
7
0
1
3
6
0
: NO
1
: YES
0
0
6
3
63
0
1
0
1
0
1
0
1
0
1
2
3
1
2
3
Field Settings