SiUS341615E
∗1. Pull out and insert the connector once and check it is absolutely connected.
Note:
∗2. Method to check transmission part of indoor unit main PCB.
Service Diagnosis
(1) Turn OFF the power and remove the connector X70A of indoor unit PCB (A1P).
(2) Short circuit X70A.
(3) After turning ON the power, check below numbers under field setting from remote controller.
(Confirmation: Second code No. at the condition of first code No. 21 on mode No. 41)
Determination
01: Normal
Other than 01: Transmission error on indoor unit main PCB
∗ After confirmation, turn OFF the power, take off the short circuit and connect X70A back to
original condition.
Troubleshooting by Error Code
198