Monitor Mode (Mode 1) - Daikin RXYQ-TA Series Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
2.5

Monitor Mode (Mode 1)

In the monitor mode, information can be retrieved about settings related to performance, addresses, number of
units and actual operation data.
2.5.1 Retrieve Data by Using BS Button Outdoor Unit Main PCB
To enter "monitor mode", press the
MODE (BS1) button while in
"normal mode".
<Selecting monitoring item>
Press the SET (BS2) button to set
the 7 segment display to any of the
monitoring items listed in the table on the
following page.
<Checking for description of data>
Press the RETURN (BS3) button.
Data on the monitoring item selected will
appear on the 7 segment display.
Press the RETURN (BS3) button to
set "Monitoring mode" to the initial state.
Press the MODE (BS1) button will
return the mode to "normal mode".
∗ If you lose setting in progress,
press the MODE (BS1) button.
You should return to "normal mode".
Legend Segment
Field Settings
: OFF
: ON
Field Settings for Outdoor Unit
SEG1 SEG2 SEG3
Normal
BS1
MODE
BS2
SET
BS3
RETURN
BS3
RETURN
BS1
MODE
Normal
: BLINKS
: hold 5 seconds
126