Refrigerant Circuit
1.2

Indoor Unit

No. in piping
Name
diagram
Electronic expansion
(1)
valve
(2)
Suction air thermistor
(3)
Liquid pipe thermistor
(4)
Gas pipe thermistor
(5)
Discharge air thermistor
∗1. R1T is for remote controller thermistor or optional remote sensor.
FXFQ-T, FXFQ-P, FXHQ-M
Indoor heat exchanger
Fan
(3)
(2)
Filter
Filter
(1)
FXUQ-P, FXEQ-P, FXMQ-M, FXAQ-P, FXLQ-M,
FXNQ-M
Indoor heat exchanger
Fan
(3)
(2)
Filter
Filter
(1)
15
Symbol
Except
FXMQ-PB,
FXMQ-PB
FXTQ-TA
Y1E
Y1E
R1T
R1T
R2T
R2T
R3T
R3T
R4T
Gas piping
connection port
(4)
Liquid piping
connection port
C: 4D024460M
Gas piping
connection port
(4)
Liquid piping
connection port
C: 4D034245P
FXTQ-TA
Used for gas superheated degree control while
Y1E
in cooling or subcooled degree control while in
heating.
R1T (∗1)
Used for thermostat control.
Used for gas superheated degree control while
R2T
in cooling or subcooled degree control while in
heating.
Used for gas superheated degree control while
R3T
in cooling.
Used for discharge air temperature control.
FXZQ-M
Indoor heat exchanger
Fan
(3)
(2)
Filter
Filter
(1)
FXDQ-M
Gas piping connection port
Liquid piping connection port
(3)
Filter
(4)
Indoor heat exchanger
SiUS341615E
Function
Gas piping
connection port
(4)
Liquid piping
connection port
C: 4D040157B
Filter
(1)
(2)
Fan
C: 4D043864N
Refrigerant Circuit

Hide quick links:

Advertisement

Table of Contents
loading