When operation parameters return to normal range, the capacity priority is switched OFF, enable to
reduce airflow rate depending on night-time low noise operation is still required (end time for night-time
low noise operation is not reached or external input night-time low noise operation is still closed).
Operation
sound
Rated
operation
sound
Operation
sound
of mode 1
Operation
sound
of mode 2
Operation
Low noise mode
sound
instructing
of mode 3
Operation sound set with
"External low noise setting"
[2-30]: Power consumption limitation level (step 1) via the external control adaptor (DTA104A61/62)
If the system needs to be running under power consumption limitation conditions when an external signal
is sent to the unit, this setting defines the level power consumption limitation that will be applied for step 1.
The level is according to the table.
3 (default)
[2-31]: Power consumption limitation level (step 2) via the external control adaptor (DTA104A61/62)
If the system needs to be running under power consumption limitation conditions when an external signal
is sent to the unit, this setting defines the level power consumption limitation that will be applied for step 2.
The level is according to the table.
1 (default)
Field Settings
Time set with "Night-time low
noise operation start setting"
20:00
22:00
Set with "Night-time low noise operation start
setting". (Factory setting is "22:00".)
Value
Power consumption limitation
[2-30]
1
2
4
5
6
7
8
Value
Power consumption limitation
[2-31]
2
3
If capacity priority is set in
"Capacity priority setting", the fan
speed will be increased
according to the load of air
conditioning when load is heavier.
∗Night-time
∗Low noise
∗Operation sound mode
mode instructing
set with "Night-time low
noise operation setting"
∗Operation sound set with
"External low noise setting"
24:00
(approximately)
60%
65%
70%
75%
80%
85%
90%
95%
(approximately)
40%
50%
55%
Field Settings for Outdoor Unit
Time set with "Night-time low
noise operation end setting"
6:00 7:00 8:00
Set with "Night-time low noise operation end
setting". (Factory setting is "8:00".)