Daikin RXYQ-TA Series Service Manual page 169

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
[2-97]: Auxiliary heater maximum allowable temperature release differential
Auxiliary heater is not allowed to energize when the outdoor ambient temperature is recovered by
differential above the auxiliary heater maximum allowable temperature.
1 (default)
Field Settings
Value
Auxiliary heater maximum allowable
[2-98]
temperature release differential
0
2
2.8°C (5°F)
5.6°C (10°F)
8.3°C (15°F)
Field Settings for Outdoor Unit