Field Settings for Outdoor Unit
2.3

Settings by BS Buttons

The following settings can be made using the BS buttons on the PCB.
In case of a multi outdoor system, make these settings with the master outdoor unit (settings made with a slave
unit are disabled).
BS buttons
BS1
MODE
Used to make
setting mode
changes.
Normal mode:
Blank: If no abnormality is detected and initialization of communication was completed.
Flashing combination of letter and number (4 digits): Error code detected by outdoor control or trouble by
communication.
Setting mode: Used to make changes to operating status, performance settings or address setting.
Monitor mode: Used to verify contents of settings, quantity of units, current value of some parameters during
Mode changing procedure can be selected using the BS1 (MODE) button as shown below:
Setting mode
SEG1 SEG2 SEG3
123
BS2
BS3
SET
RETURN
(TEST)
(RESET)
Used to make
field settings.
operation of outdoor unit.
Press and hold the
BS1 (MODE) for 5
seconds or more
Press the BS1 (MODE) once
7 segment display (SEG1-3)
Normal mode
Setting mode
Monitor mode
Press the BS1 (MODE) once
Normal mode
SEG1 SEG2 SEG3
SiUS341615E
SEG1 SEG2 SEG3
Monitor mode
SEG1 SEG2 SEG3
Field Settings