Setting Mode (Mode 2) - Daikin RXYQ-TA Series Service Manual

Heat pump 60 hz
Table of Contents

Advertisement

SiUS341615E
2.6

Setting Mode (Mode 2)

Press and hold the MODE (BS1)
button for 5 seconds or more and
set to "Setting mode".
<Selection of setting items>
Press the SET (BS2) button and set
the 7 segment display to a setting
item shown in the table on the
following page.
Press the RETURN (BS3) button
and decide the item. (The present
setting condition is blinked.)
<Selection of setting conditions>
Press the SET (BS2) button and set
to the setting condition you want.
Press the RETURN (BS3) button
and decide the condition.
Press the RETURN (BS3) button
and set to the initial status of
"Setting mode".
Press the MODE (BS1) button to
return to "Normal mode".
∗ If you become unsure of how to
proceed, press the MODE (BS1)
button and return to "Normal mode".
Legend Segment
Field Settings
BS1
MODE
BS2
SET
BS3
RETURN
BS2
SET
BS3
RETURN
BS3
RETURN
BS1
MODE
: OFF
: ON
SEG1 SEG2 SEG3
: BLINKS
: hold 5 seconds
Field Settings for Outdoor Unit
Normal
Default
Normal
140