Operation of Downward Flow Flap (for FXEQ model)
When only the front-flow is used, sets yes/no of the swing flap operation of down-flow.
Mode No.
13 (23)
Setting of Airflow Direction Adjustment Range
Make the following airflow direction setting according to the respective purpose.
Mode No.
13 (23)
∗Some indoor unit models are not equipped with draft prevention (upward) function.
Setting of the Static Pressure Selection (for FXDQ model)
Model No.
13 (23)
External Static Pressure Settings (for FXMQ-PB model)
Mode No.
13 (23)
The Second Code No. is set to 07 (an external static pressure of 100 Pa (0.40 inWG)) at factory setting.
∗1. FXMQ15/18/24/30/36/48PB cannot be set to 30 Pa (0.12 inWG).
∗2. FXMQ07/09/12PB cannot be set to 110-200 Pa (0.44-0.80 inWG).
∗3. FXMQ54PB cannot be set to 30 Pa (0.12 inWG) or 150-200 Pa (0.60-0.80 inWG).
Field Settings
First Code No.
Second Code No.
3
First Code No.
Second Code No.
4
First Code No.
Second Code No.
5
First Code No.
Second Code No.
6
01
02
01
02
03
Downward (Ceiling soiling prevention)
Standard (FXDQ07-12: 10 Pa (0.04 inWG),
01
FXDQ18/24: 30 Pa (0.12 inWG))
02
(FXDQ07-12: 15 Pa (0.06 inWG),
FXDQ18/24: 45 Pa (0.18 inWG))
01
02
03
04
05
06
07
08
09
10
11
12
150 Pa (0.60 inWG) (∗2) (∗3)
13
160 Pa (0.64 inWG) (∗2) (∗3)
14
180 Pa (0.72 inWG) (∗2) (∗3)
15
200 Pa (0.80 inWG) (∗2) (∗3)
Field Setting from Remote Controller
Contents
Equipped
Not equipped
Contents
Upward (Draft prevention)
Standard
Contents
High static pressure
Contents
30 Pa (0.12 inWG) (∗1) (∗3)
50 Pa (0.20 inWG)
60 Pa (0.24 inWG)
70 Pa (0.28 inWG)
80 Pa (0.32 inWG)
90 Pa (0.36 inWG)
100 Pa (0.40 inWG)
110 Pa (0.44 inWG) (∗2)
120 Pa (0.48 inWG) (∗2)
130 Pa (0.52 inWG) (∗2)
140 Pa (0.56 inWG) (∗2)
112