Daikin RXYQ-TA Series Service Manual page 124

Heat pump 60 hz
Table of Contents

Advertisement

Field Setting from Remote Controller
Setting of Airflow Rate
Make the following setting according to the ceiling height. The second code No. is set to 01 at the factory.
FXHQ, FXAQ
Mode No.
13 (23)
FXFQ07-24T, FXFQ09-30P, FXUQ18/24P
Mode No.
13 (23)
FXFQ30-48T, FXFQ36/48P, FXUQ30/36P
Mode No.
13 (23)
Airflow Direction Setting
Set the airflow direction of indoor units as given in the table below. (Set when sealing material kit of air discharge
outlet has been installed.) The second code No. is factory set to 01.
Mode No.
13 (23)
Swing Pattern Settings
(For units with the infrared presence sensor only)
Set the flap operation in swing mode.
With the factory swing, flaps facing each other are synchronized to operate, and flaps placed side by side are set
to swing in an opposite direction to agitate airflow to reduce temperature irregularity.
Conventional swing operation (all direction synchronized swing) can be set onsite.
Mode No.
13 (23)
111
First Code No.
Second Code No.
0
First Code
Second
No.
Code No.
01
0
02
03
First Code
Second
No.
Code No.
01
0
02
03
First Code No.
Second Code No.
1
First Code No.
Second Code No.
2
01
02
03
Contents
4-way Outlets
Lower than
Standard
(8-3/4 ft)
Lower than
High Ceiling 1
Lower than
Higher Ceiling 2
(11-1/2 ft)
Contents
4-way Outlets
Lower than
Standard
(10-1/2 ft)
Lower than
High Ceiling 1
Lower than
Higher Ceiling 2
(13-3/4 ft)
01
F: 4-direction airflow
02
T: 3-direction airflow
03
W: 2-direction airflow
01
02
03
Contents
Standard
Slight increase
Normal increase
Ceiling height
3-way Outlets
Lower than
2.7 m
3.0 m
(10 ft)
Lower than
3.0 m
3.3 m
(10 ft)
(10-3/4 ft)
Lower than
3.5 m
3.5 m
(11-1/2 ft)
Ceiling height
3-way Outlets
Lower than
3.2 m
3.6 m
(12 ft)
Lower than
3.6 m
4.0 m
(12 ft)
(13-1/8 ft)
Lower than
4.2 m
4.2 m
(13-3/4 ft)
Contents
Contents
All direction synchronized swing
Facing swing
SiUS341615E
2-way Outlets
Lower than
3.5 m
(11-1/2 ft)
Lower than
3.8 m
(12-1/2 ft)
2-way Outlets
Lower than
4.2 m
(13-3/4 ft)
Lower than
4.2 m
(13-3/4 ft)
Field Settings