Check Fieldbus Communication; Check Profibus-Dp Configuration - Festo CTEU-PB Electronics Description

Universal bus node, fieldbus protocol profibus-dp
Table of Contents

Advertisement

4. Error handling

4.1.4 Check fieldbus communication

LED normal status

4.1.5 Check PROFIBUS-DP configuration

Problem description:
Remedy
Problem description:
Remedy
Festo P.BE-CTEU-PB-OP+MAINT-EN en 1208NH English
Compare the desired station address with the station ad-
dress set on the bus node (DIL switch setting).
Information on installation of the bus node can be found in
chap. 1.
Compare your selected cable lengths with the technical
data in the appendix and the recommendations in
chap. 1.5.1.
Check the installation of the bus terminals at both ends of
the fieldbus.
BF LED is off (in DataEx mode).
Process data are defective.
Proceed as follows:
1. Check at the controller the set process data ranges for
consistency (not too small/large, without overlapping,
unused ranges, ...)
2. Check whether the force/control data are correct or if
manually set statuses have to be reset.
3. Check at your master whether the configuration or para-
meter data are correct, since otherwise no process data
exchange will take place.
Outputs do not switch to the desired status if fieldbus com-
munication is disrupted.
Proceed as follows: