1. Installation
1.4.2 Setting the DIL switches
1
DIL switches
1 ... 7: station ad-
dress
2
DIL switches
8 ... 10: reserved
(standard setting:
OFF)
3
DIL switch 11:
diagnostics mode
4
DIL switch 12:
Fail state mode
Fig. 1/2: DIL switch groups in the bus node
1-10
Proceed as follows:
1. Switch off the power supply.
2. Remove the DIL switch cover (chap. 1.4.1).
3. Assign a still unused station address to the bus node.
4. Activate/deactivate the diagnostics mode.
5. Set the Fail state characteristics.
6. Mount the DIL switch cover (chap. 1.4.1).
1
2
3
Festo P.BE-CTEU-PB-OP+MAINT-EN en 1208NH English