Reading Diagnostic Information; Implemented Functions And Service Access Points (Sap - Festo CTEU-PB Electronics Description

Universal bus node, fieldbus protocol profibus-dp
Table of Contents

Advertisement

A. Technical appendix
A.3.4 Reading diagnostic information
Slave_Diag
Set_Prm
A.3.5 Implemented functions and service access points (SAP)
A-18
The diagnostic data are requested by the bus node with the
function Slave_Diag (see chap. 3.3.3).
With the function Set_Prm you can determine the watchdog
time (WD_Fact_1, Octet 2, WD_Fact_2, Octet 3).
The behaviour of the bus node in case of error (e.g. bus fail-
ure) depends on the parameterisation (see chap. 2.8).
Function
Data_Exchange
RD_Inp
RD_Outp
Slave_Diag
*)
Set_Prm
Chk_Cfg
Get_Cfg
Global_Control
Set_Slave_Add
MSAC_C1
MSAC_C2
*) The bus node parameters are also sent with Set_Prm during the
initialisation phase.
Tab. A/8:
Overview of functions and service access points
Available
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
Yes
No
Festo P.BE-CTEU-PB-OP+MAINT-EN en 1208NH English
Destination SAP
(DSAP)
NIL
56
57
60
61
62
59
58
55
50, 51