1. Installation
Cable length (approximate values) dependent on the data rate (baud rate)
1)
Baud rate
1.5 MBaud
3 ... 12 MBaud
1)
The baud rates named here are approximate values and are not supported by all masters.
2)
Trunk line
3)
Drop line
Tab. 1/2:
Maximum cable lengths (approximate values)
1.5.4 Fieldbus interface at the bus node
Festo P.BE-CTEU-PB-OP+MAINT-EN en 1208NH English
2)
Segment length
Max. 200 m
Max. 100 m
There is a 9-pin sub-D socket on the bus node for connection
to the fieldbus.
This connection is used for the supply line and continuation
of the fieldbus cable. Connect the bus node with the fieldbus
plug from Festo type FBS-SUB-9-GS-DP-B.
Note
Before connecting the sub-D plugs of other manufacturers:
Replace the two flat screws with bolts
•
(type UNC 4-40/M3x5) from Festo accessories
(
Accessories
Branch line length
Max. 6.6 m
–
www.festo.com/catalogue).
3)
(total)
1-15