Operation With The General Dp Master; Sending Parameterisation Data - Festo CTEU-PB Electronics Description

Universal bus node, fieldbus protocol profibus-dp
Table of Contents

Advertisement

A. Technical appendix
A.3

Operation with the general DP master

A.3.1 Sending parameterisation data
Set_Prm
Octet 1: Station status
Bit
Significance
0
1
2
3
WD_On
4
Freeze_Req
5
Sync_Req
6
Unlock_Req
7
Lock_Req
Tab. A/5:
Octet 1: Station status
A-14
The parameterisation data is transferred from the DP master
to the bus node with the function Set_Prm.
Explanation
Reserved
Response monitoring of the bus node on/off:
0 = off
1 = on
0 = FREEZE mode not required by the master
1 = FREEZE mode set by the master
0 = SYNC mode not required by the master
1 = SYNC mode set by the master
Bit 7
Bit 6
Explanation
0
0
Min. T
SDR
0
1
Bus node is approved for other masters
1
0
Bus node is blocked for other masters
1
1
Bus node is approved for other masters
+ slave parameters may be overwritten
Festo P.BE-CTEU-PB-OP+MAINT-EN en 1208NH English