Fail State Behaviour - Festo CTEU-PB Electronics Description

Universal bus node, fieldbus protocol profibus-dp
Table of Contents

Advertisement

2. Commissioning
2.8

Fail state behaviour

Parameterisation
2-40
Fail state regulates the behaviour of the bus node and the
connected equipment in the event of communication mal-
functions.
The behaviour of the bus node is dependent on the DIL switch
setting (see chap. 1.4) and the configured behaviour of the
master in the case of:
telegram failure
interruption of the fieldbus line
Depending on the parameterisation, the outputs (valves and
electric outputs) will be switched off (factory setting),
switched on or retain their status (see Tab. 2/10).
Warning
An incorrect status of the valves and outputs can lead to
dangerous situations!
Ensure that valves and outputs are put into a safe status
if the stated malfunctions occur.
Note
Please observe the following if the outputs are reset in the
event of fieldbus interruptions or malfunctions:
– Monostable valves move to the basic position
– Bistable valves remain in the current position
– Mid-position valves go into mid-position (pressurized,
exhausted or closed, depending on valve type).
Festo P.BE-CTEU-PB-OP+MAINT-EN en 1208NH English