3. Diagnostics
Bit
Significance
1
Diag.Stat_Diag
2
3
Diag.WD_On
4
Diag.Freeze_Mode
5
Diag.Sync_Mode
6
7
Diag.Deactivated
bold = bus-node-related bits
Tab. 3/9:
Diagnostic bits station status_2
Station status_3
Bit
Significance
0 ... 6
7
Diag.Ext_Diag_Overflow
Tab. 3/10: Diagnostic bits Station status_3

3.3.4 Details of the channel-related diagnostics

3-14
Explanation
Bit = 1: Master must fetch diagnostic data until this bit is
set to 0
Bit = 1: Bus node does not support the function requested
Bit = 1: Response monitoring/watchdog activated
Bit = 1: Freeze activated
Bit = 1: SYNC activated
Reserved
Bit = 0 (set by the bus node)
Explanation
Reserved
Bit = 1: Bus node has more diagnostic messages than can
be buffered or master includes more diagnostic messages
than it can buffer.
Through the channel-related diagnostics, detailed diagnostic
information is transferred by port. For each channel, 3 bytes
of diagnostic data are available (see Fig. 3/4):
Byte 1: module number
Byte 2: module type
Byte 3: type of diagnostics
Festo P.BE-CTEU-PB-OP+MAINT-EN en 1208NH English