3. Diagnostics
Device-specific diagnostics (16 bytes), (module status DPV1)
Byte
Contents
7
Header
8
Type
9
Slot
10
Slot
11
Module 0 (bit 1 and 2)
...
Module 3 (bit 6 and 7)
12
Module 4...7
13
Module 8...10
(bits 6 and 7 are reserved)
14...22
Reserved
Tab. 3/6:
Diagnostic bytes 7 ... 22: device-specific diagnostics (fixed at a length of 16
bytes)
Module-related diagnostics (variable length)
Byte
Contents
1
Header
2
Module-related diagnostics
Tab. 3/7:
Module-related diagnostics
3-12
Explanation
For the bus node fixed 04h
For the bus node fixed 81h
For the bus node fixed 0
For the bus node fixed 0
2 bits per module:
00 = no error (valid user data)
01 = module error (invalid user data)
10 = incorrect module (invalid user data)
11 = module failed or is not on hand (invalid user
data)
like byte 11
like byte 11
Explanation
For the bus node fixed 42
Specifies the module number with diagnostics.
Festo P.BE-CTEU-PB-OP+MAINT-EN en 1208NH English