AGC 200 installation instructions
4189340610 UK
Positive sequence: < 60 ms
Time-dependent under-voltage, U
Under-voltage and reactive power low, U
UL markings
Wiring: Use 60/75 °C copper conductors only
Wire size: AWG 30-12
Terminal tightening torque: 5-7 lb-in
Mounting: For use on a flat surface of a type 1 enclosure
Installation: To be installed in accordance with the NEC (US) or the CEC (Canada)
DEIF A/S
< < 50 ms
t
< <250 ms
Q
Technical information
Page 67 of 67