Functions
7.1 PROFIenergy
7.1.1

Energy saving function command

Command "PE_Energy_Saving_Function"
The 3RW44 soft starter distinguishes between two different data transmission modes:
PE_Mode_ID = 255
PE_Mode_ID = 01
t
off
t
off_min
t
on
t
Pause_min
Note
A pending fault is not acknowledged by the switchover to energy saving mode, i.e., the
pending fault is saved internally and can be read. When energy saving mode is exited, the
fault must be eliminated and acknowledged.
44
Ready to operate
Energy saving mode
Time_to_Pause
Time_min_length_of_stay
Time_to_operate
Time_min_Pause
Time the soft starter requires in order to change to energy
saving mode. For the 3RW44 soft starter, this time is 200 ms.
An assigned ramp-down time is added to this (if available and
if the starter was in the ON state):
t
= 200 ms + ramp-down time
off
If the soft starter was already off before the pause, energy
saving mode will be switched to after only 200 ms.
Minimum time that the device spends or should spend in
energy saving mode.
For 3RW44: 0 ms
Time that will elapse before the starter changes back to the
operating state. Since the process image is evaluated again
immediately when the 3RW44 exits energy saving mode, this
time is 0 ms.
Time that is compared with t
the "Start_Pause" command to the soft starter); if t
t
, the device switches to energy saving mode.
Pause_min
PROFINET Communication Module for SIRIUS Soft Starter 3RW44
Manual, 12/2013, A5E31996495002A/RS-AA/001
(is transferred together with
Pause
Pause